5-57 Term. 33 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Enter the low reference value
[RPM] for the motor shaft speed.
This is also the low feedback
value, see also
5-52 Term. 29 Low
Ref./Feedb. Value
.
5-58 Term. 33 High Ref./Feedb. Value
Range:
Function:
Application
dependent
*
[-999999.999 -
999999.999
ReferenceFeedbackUnit]
Enter the high
reference value [RPM]
for the motor shaft
speed. See also
5-53 Term. 29 High
Ref./Feedb. Value
.
Application
dependent
*
[-999999.999 -
999999.999
ReferenceFeedbackUnit]
5-59 Pulse Filter Time Constant #33
Range:
Function:
100 ms
*
[1 - 1000
ms]
Enter the pulse filter time constant. The
low-pass filter reduces the influence on,
and dampens oscillations in, the feedback
signal from the control.
This is an advantage, if, for example, there
is a great amount of noise in the system.
NOTE!
This parameter cannot be adjusted while the motor is
running.
3.7.6 5-6* Pulse Outputs
These parameters are to configure pulse outputs with their
functions and scaling. Terminal 27 and 29 are allocated to
pulse output via
5-01 Terminal 27 Mode
and
5-02 Terminal
29 Mode
, respectively.
NOTE!
These parameters cannot be adjusted while the motor is
running.
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Options for readout output variables:
Parameters for configuring the
scaling and output functions of
pulse outputs. The pulse outputs
are designated for terminals 27 or
29. Select terminal 27 output in
5-01 Terminal 27 Mode
and
terminal 29 output in
5-02 Terminal 29 Mode
.
[0]
No operation
[45]
Bus control
[48]
Bus control timeout
[51]
MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative to limit
[105] Torque relative to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
*
No operation
Select the desired display output for
terminal 27.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-65