35-25 Term. X48/7 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/7. The temperature limits
can be set in
35-26 Term. X48/7 Low Temp. Limit
and
35-27 Term.
X48/7 High Temp. Limit
.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-26 Term. X48/7 Low Temp. Limit
Range:
Function:
Application dependent
*
[Application dependant]
35-27 Term. X48/7 High Temp. Limit
Range:
Function:
Application dependent
*
[Application dependant]
3.21.4 35-3* Temp. Input X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/10. A high time constant
value improves dampening but also
increases the time delay through the
filter.
35-35 Term. X48/10 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/10. The temperature limits
can be set in
35-36 Term. X48/10 Low Temp. Limit
/
35-37 Term.
X48/10 High Temp. Limit
.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-36 Term. X48/10 Low Temp. Limit
Range:
Function:
Application dependent
*
[Application dependant]
35-37 Term. X48/10 High Temp. Limit
Range:
Function:
Application dependent
*
[Application dependant]
3.21.5 35-4* Analog Input X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
Function:
4.00
mA
*
[Application
dependant]
Enter the current (mA) that
corresponds to the low reference
value, set in
35-44 Term. X48/2 Low
Ref./Feedb. Value
. The value must be
set at > 2mA in order to activate the
Live Zero Timeout Function in
6-01 Live Zero Timeout Function
.
35-43 Term. X48/2 High Current
Range:
Function:
20.00 mA
*
[Application
dependant]
Enter the current (mA) that
corresponds to the high
reference value (set in
35-45 Term. X48/2 High Ref./Feedb.
Value
).
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Enter the reference or feedback
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in
35-42 Term. X48/2
Low Current
.
35-45 Term. X48/2 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Enter the reference or feedback
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in
35-43 Term. X48/2
High Current
.
35-46 Term. X48/2 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/2. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-155