2-26 Torque Ref
Range:
Function:
0.00 %
*
[Application
dependant]
The value defines the torque
applied against the closed
mechanical brake before release
2-27 Torque Ramp Time
Range:
Function:
0.2 s
*
[0.0 - 5.0 s] The value defines the duration of the torque
ramp in clockwise direction.
2-28 Gain Boost Factor
Range:
Function:
1.00
*
[1.00 -
4.00 ]
Only active in flux closed-loop. The function
ensures a smooth transition from torque
control mode to speed control mode when
the motor takes over the load from the
brake.
Mech.Brake
GainBoost
Relay
Torqueref.
MotorSpeed
Premag
Torque Ramp
Time
p. 2-27
Torque Ref. 2-26
Gain Boost Factor
p. 2-28
Brake
Release
Time
p. 2-25
Ramp 1 upp. 3-41
Ramp 1 downp. 3-42
Stop
Delay
p. 2-24
Activate
Brake
Delay
p. 2-23
1
2
3
130BA642.12
II
I
Figure 3.8 Brake release sequence for hoist mechanical brake control
I)
Activate brake delay
: The Adjustable frequency drive starts again from the
mechanical brake engaged
position.
II)
Stop delay
: When the time between successive starts is shorter than the setting in
2-24 Stop Delay
, the Adjustable frequency drive starts
without applying the mechanical brake (e.g., reversing).
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-33
3
3