3.17 Parameters: 16-** Data Read-outs
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the
Adjustable frequency drive via the serial
communication port in hex code.
16-01 Reference [Unit]
Range:
Function:
0.000 Reference-
FeedbackUnit
*
[-999999.000 -
999999.000
ReferenceFeed-
backUnit]
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected
in
1-00 Configuration
Mode
(Hz, Nm or RPM).
16-02 Reference [%]
Range:
Function:
0.0 %
*
[-200.0 - 200.0 %]
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the Adjustable
frequency drive via the serial communication
port in hex code.
16-05 Main Actual Value [%]
Range:
Function:
0.00 %
*
[-100.00 - 100.00
%]
View the two-byte word sent with
the status word to the bus master
reporting the main actual value.
16-09 Custom Readout
Range:
Function:
0.00 CustomRea-
doutUnit
*
[0.00 - 0.00
CustomRea-
doutUnit]
View the value of custom
readout from
0-30 Unit for
User-defined Readout
to
0-32 Custom Readout Max
Value
3.17.1 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0.00
kW
*
[0.00 -
10000.00
kW]
Displays motor power in kW. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore approx.
16-10 Power [kW]
Range:
Function:
30ms may pass from when an input value
changes to when the data readout values
change. The resolution of readout value
on serial communication bus is in 10 W
steps.
16-11 Power [hp]
Range:
Function:
0.00
hp
*
[0.00 -
10000.00 hp]
View the motor power in HP. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore
approximately 30ms may pass from
when an input value changes to when
the data readout values change.
16-12 Motor Voltage
Range:
Function:
0.0 V
*
[0.0 - 6000.0 V] View the motor voltage, a calculated
value used for controlling the motor.
16-13 Frequency
Range:
Function:
0.0 Hz
*
[0.0 - 6500.0 Hz] View the motor frequency, without
resonance dampening.
16-14 Motor Current
Range:
Function:
0.00 A
*
[0.00 -
10000.00 A]
View the motor current measured as a
mean value, IRMS. The value is filtered,
and thus approximately 30ms may pass
from when an input value changes to
when the data readout values change.
16-15 Frequency [%]
Range:
Function:
0.00 %
*
[-100.00 - 100.00 %]
16-16 Torque [Nm]
Range:
Function:
0.0
Nm
*
[-3000.0 -
3000.0
Nm]
View the torque value with sign, applied to
the motor shaft. Linearity is not exact
between 160% motor current and torque in
relation to the rated torque. Some motors
supply more than 160% torque.
Consequently, the min. value and the max.
value will depend on the max. motor current
as well as the motor used. The value is
filtered, and thus approx. 30ms may pass
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-141