feature is used when Multi set-up in par.0-10
selected. Multi set-up can be used to move from one set-up to another during operation (i.e. while
the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 whilst the motor is running. Programme param-
eters in Set-up 1 first, then ensure that Set-up 1 and Set-up 2 are synchronised (or ‘linked’).
Synchronisation can be performed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in par.0-11
Set-up 1
[1]. This will start the linking (synchronising) process.
130BP075.10
OR
2. While still in Set-up 1, using par.0-50
, copy Set-up 1 to Set-up 2. Then set par.
to
Set-up 2
[2]. This will start the linking process.
130BP076.10
After the link is complete, par.0-13
will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are now the same in Set-up 1 and Set-up 2. If there are
changes to a ‘not changeable during operation’ parameter, e.g. par.1-30
, in
Set-up 2, they will also be changed automatically in Set-up 1. A switch between Set-up 1 and Set-
up 2 during operation is now possible.
[0] *
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
VLT
®
AQUA Drive Programming Guide
2 Parameter Description