25-46 Destaging Speed [RPM]
Range:
Function:
0 RPM*
[0 - 0 RPM]
Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump,
in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed.
When the variable speed pump reaches the “Destaging Speed” the fixed speed pump is destaged.
Destaging Speed is calculated based on par.25-43
Destaging Speed is calculated with the following formula:
DESTAGE
=
HIGH
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the
value of Destaging Threshold.
25-47 Destaging Speed [Hz]
Range:
Function:
0.0 Hz*
[0.0 - 0.0 Hz]
Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump,
in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed.
When the variable speed pump reaches the “Destaging Speed” the fixed speed pump is destaged.
Destaging Speed is calculated based on par.25-43
Destaging Speed is calculated with the following formula:
DESTAGE
=
HIGH
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the value of Destaging Threshold.
2.21.5 25-5* Alternation Settings
Parameters for defining the conditions for alternation of the variable speed pump (lead), if selected as part of the control strategy.