5-30 Terminal 27 Digital Output
Option:
Function:
Same options and functions as par. 5-3*.
[0] *
No operation
5-31 Terminal 29 Digital Output
Option:
Function:
Same options and functions as par. 5-3*.
[0] *
No operation
5-32 Term X30/6 Digi Out (MCB 101)
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 101 is mounted in the frequency converter.
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for operation and applies a supply signal on the control board.
[3]
Drive rdy/rem ctrl
The frequency converter is ready for operation and is in Auto On mode.
[4]
Standby / no warning
Ready for operation. No start or stop command is been given (start/disable). There are no warnings.
[5]
Running
Motor is running.
[6]
Running / no warning
Output speed is higher than the speed set in par.1-81
Min Speed for Function at Stop [RPM]
motor is running and there are no warnings.
[8]
Run on ref/no warn
Motor is running within the programmed current and speed ranges set in par. 4-50
Warning Current
Low
to par. 4-53
Warning Speed High
. There are no warnings.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in par. 4-16
Torque Limit Motor Mode
or par. 1-17 has been exceeded.
[12]
Out of current range
The motor current is outside the range set in par. 4-18
Current Limit
.
[13]
Below current, low
Motor current is lower than set in par. 4-50
Warning Current Low
.
[14]
Above current, high
Motor current is higher than set in par. 4-51
Warning Current High
.
[15]
Out of speed range
Output frequency is outside the frequency range set in par. 4-50
Warning Current Low
and
par. 4-51
Warning Current High
.
[16]
Below speed, low
Output speed is lower than the setting in par. 4-52
Warning Speed Low
.
[17]
Above speed, high
Output speed is higher than the setting in par. 4-53
Warning Speed High
.
[18]
Out of feedb. range
Feedback is outside the range set in par. 4-56
Warning Feedback Low
and par. 4-57
Warning Feed-
back High
.
[19]
Below feedback, low
Feedback is below the limit set in par. 4-56
Warning Feedback Low
.
[20]
Above feedback, high
Feedback is above the limit set in par. 4-57
Warning Feedback High
.
[21]
Thermal warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency
converter, the brake resistor, or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’
when CW rotation of the motor. Logic ‘0’ when CCW rotation of the motor. If
the motor is not rotating the output will follow the reference.
[26]
Bus OK
Active communication (no time-out) via the serial communication port.
[27]
Torque limit & stop
Use in performing a coasting stop and in torque limit condition. If the frequency converter has
received a stop signal and is at the torque limit, the signal is Logic ‘0’.
[28]
Brake, no brake war
Brake is active and there are no warnings.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark