3-17 Reference 3 Source
Option:
Function:
Select the reference input to be used for the third reference signal. par.3-15
define up to three different reference
signals. The sum of these reference signals defines the actual reference.
This parameter cannot be adjusted while the motor is running.
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
3-19 Jog Speed [RPM]
Range:
Function:
300. RPM* [0 - par. 4-13 RPM]
Enter a value for the jog speed n
JOG
, which is a fixed output speed. The frequency converter runs
at this speed when the jog function is activated. The maximum limit is defined in par. .
See also par.3-80
2.5.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of the two ramps (par. 3-4* and par. 3-5*).
VLT
®
AQUA Drive Programming Guide
2 Parameter Description