[62]
Comparator 2
See par. group 13-1*. If Comparator 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[63]
Comparator 3
See par. group 13-1*. If Comparator 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[64]
Comparator 4
See par. group 13-1*. If Comparator 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[65]
Comparator 5
See par. group 13-1*. If Comparator 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[70]
Logic Rule 0
See par. group 13-4*. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[71]
Logic Rule 1
See par. group 13-4*. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[72]
Logic Rule 2
See par. group 13-4*. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[73]
Logic Rule 3
See par. group 13-4*. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[74]
Logic Rule 4
See par. group 13-4*. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[75]
Logic Rule 5
See par. group 13-4*. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[80]
SL Digital Output A
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [38]
Set
dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [32] Set dig.
out. A low is executed.
[81]
SL Digital Output B
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [39]
Set
dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [33]
Set dig.
out. A low
is executed.
[82]
SL Digital Output C
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [40]
Set
dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [34]
Set dig.
out. A low
is executed.
[83]
SL Digital Output D
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [41]
Set
dig. out. A
high is executed. The input will go low whenever the Smart Logic Action [35]
Set dig.
out. A low
is executed.
[84]
SL Digital Output E
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [42]
Set
dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [36]
Set dig.
out. A low
is executed.
[85]
SL Digital Output F
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [43]
Set
dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [37]
Set dig.
out. A low
is executed.
[160]
No alarm
Output is high when no alarm is present.
[161]
Running reverse
The output is high when the frequency converter is running counter clockwise (the logical product
of the status bits ‘running’ AND ‘reverse’).
[165]
Local reference active
Output is high when par. 3-13
Reference Site
= [2] Local or when par. 3-13
Reference Site
= [0]
Linked to hand auto
at the same time as the LCP is in Hand on mode.
[166]
Remote reference active
Output is high when par. 3-13
Reference Site = Remote
[1] or
Linked to hand/auto
[0] while the
LCP is in [Auto on] mode.
[167]
Start command active
Output is high when there is an active Start command. (I.e.[Auto On] and a start command via
digital input or bus is active, or [Hand On].
NB!
All inverse Stop/Coast commands must be inactive.
[168]
Drive in hand mode
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light
above [Hand on].