2.12 Main Menu - Smart Logic - Group 13
2.12.1 13-** Prog. Features Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user defined actions (see par.13-52
[x]) executed by the SLC when the
associated user defined
event
(see par.13-51
[x]) is evaluated as TRUE by the SLC. Events and
actions
are each numbered and linked
together in pairs. This means that when
event
[0] is fulfilled (attains the value TRUE),
action
[0] is executed. After this, the conditions of
event
[1] will
be evaluated and if evaluated TRUE,
action
[1] will be executed and so on. Only one
event
will be evaluated at any time. If an
event
is evaluated as
FALSE, nothing happens (in the SLC) during the current scan interval and no other
events
will be evaluated. This means that when the SLC starts, it
evaluates
event
[0] (and only
event
[0]) each scan interval. Only when
event
[0] is evaluated TRUE, will the SLC execute
action
[0] and start evaluating
event
[1]. It is possible to programme from 1 to 20
events
and
actions
.
When the last
event
/
action
has been executed, the sequence starts over again from
event
[0] /
action
[0]. The illustration shows an example with three
event / actions:
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting
On
[1] or
Off
[0] in par.13-00
. The SLC always starts in state 0 (where it
evaluates
event
[0]). The SLC starts when the Start Event (defined in par.13-01
) is evaluated as TRUE (provided that
On
[1] is selected in
). The SLC stops when the
Stop Event
resets all SLC parameters and
starts programming from scratch.
2.12.2 13-0* SLCLC-0# LC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
13-00 SL Controller Mode
Option:
Function:
[0] *
Off
Disables the Smart Logic Controller.
[1]
On
Enables the Smart Logic Controller.
13-01 Start Event
Option:
Function:
Select the boolean (TRUE or FALSE) input to activate Smart Logic Control.
[0] *
False
Enters the fixed value of FALSE in the logic rule.
[1]
True
Enters the fixed value TRUE in the logic rule.
[2]
Running
See parameter group 5-3* for further description.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
119
2