9-71 Profibus Save Data Values
Option:
Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
[0] *
Off
Deactivates the non-volatile storage function.
[1]
Store all setups
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
[2]
Store all setups
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option:
Function:
[0] *
No action
[1]
Power-on reset
Resets frequency converter upon power-up, as for power-cycle.
[3]
Comm option reset
Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.
par.9-18
.
When reset, the frequency converter disappears from the fieldbus, which may cause a communi-
cation error from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A*
[0 - 9999 N/A]
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A*
[0 - 9999 N/A]
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A*
[0 - 9999 N/A]
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
9-83 Defined Parameters (4)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A*
[0 - 9999 N/A]
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
111
2