[169]
Drive in auto mode
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light
above [Auto on].
[180]
Clock Fault
The clock function has been reset to default (2000-01-01) because of a power failure.
[181]
Preventive Maintenance
One or more of the Preventive Maintenance Events programmed in par. 23-10, Preventive Mainte-
nance Item, has passed the time for the specified action in par. 23-11, Maintenance Action.
[190]
No-Flow
A No-Flow situation or Minimum Speed situation has been detected if enabled in
Minimum Speed
Detection
. par. 22-21 and/or
No-Flow Detection
, par. 22-22.
[191]
Dry Pump
A Dry Pump condition has been detected. This function must be enabled in par. 22-26, Dry Pump
Function.
[192]
End of Curve
Active when an End of Curve condition is present.
[193]
Sleep Mode
The frequency converter/system has turned into sleep mode. See
Sleep mode
, par. 22-4*.
[194]
Broken Belt
A Broken Belt condition has been detected. This function must be enabled in par. 22-60, Broken
Belt Detection.
[195]
Bypass Valve Control
The bypass valve control (Digital / Relay output in the frequency converter) is used for compressor
systems to unload the compressor during start-up by using a bypass valve. After the start command
is given the bypass valve will be open until the frequency converter reaches
Motor speed low lim-
it
, par. 4 -11) . After the limit has been reached the bypass valve will be closed, allowing the
compressor to operate normally. This procedure will not be activated again before a new start is
initiated and the frequency converter speed is zero during the receiving of start signal.
Start De-
lay
, par. 1-71 can be used in order to delay the motor start. The Bypass valve control principle:
The below setting options are all related to the Cascade Controller.
Wiring diagrams and settings for parameter, see group 25-** for more details.
[199]
Pipe Filling
Active when the Pipe Fill function is operating. See par. 29-0*.
[200]
Full Capacity
All pumps running and at full speed
[201]
Pump1 Running
One or more of the pumps controlled by the Cascade Controller are running. The function will also
depend on the setting of in
Fixed Lead Pump
, par. 25-06. If set to
No
[0] Pump 1 refers to the pump
controlled by relay RELAY1 etc. If set to
Yes
[1] Pump 1 refers to the pump controlled by the
frequency converter only (without any of the build in relays involved) and Pump 2 to the pump
controlled by the relay RELAY1. See below table:
[202]
Pump2 Running
See [201]
[203]
Pump3 Running
See [201]
Setting in Par. 5-3*
Setting in Par. 25-06
[0] No
[1] Yes
[200] Pump 1 Running
Controlled by RELAY1
Frequency Converter controlled
[201] Pump 2 Running
Controlled by RELAY2
Controlled by RELAY1
[203] Pump 3 Running
Controlled by RELAY3
Controlled by RELAY2
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
72