
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
26-61 Terminal X42/11 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale the minimum output of the selected analog signal at terminal X42/11, as a percentage of the
maximum signal level. E.g. if a 0 V is desired at 25% of the maximum output value. Then programme
25%. Scaling values up to 100% can never be higher than the corresponding setting in par.
26-62
See principle graph for par.6-51
26-62 Terminal X42/11 Max. Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
Scale the maximum output of the selected analog signal at terminal X42/9. Set the value to the
maximum value of the voltage signal output. Scale the output to give a voltage lower than 10V at
full scale; or 10V at an output below 100% of the maximum signal value. If 10V is the desired output
current at a value between 0-100% of the full-scale output, programme the percentage value in the
parameter, i.e. 50% = 10V. If a voltage between 0 and 10V is desired at maximum output, calculate
the percentage as follows:
(
10
V
desired
maximum
voltage
)
x
100 %
i.e.
5
V
: 10
V
5
V x
100 % = 200 %
See principle graph for par.6-52
26-63 Terminal X42/11 Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the level of terminal X42/11 if controlled by bus.
26-64 Terminal X42/11 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the preset level of terminal X42/11.
In case a bus time-out and a time-out function are selected, the output will preset to this level.
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
232
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2