[3]
In range
See parameter group 5-3* for further description.
[4]
On reference
See parameter group 5-3* for further description.
[5]
Torque limit
See parameter group 5-3* for further description.
[6]
Current limit
See parameter group 5-3* for further description.
[7]
Out of current range
See parameter group 5-3* for further description.
[8]
Below I low
See parameter group 5-3* for further description.
[9]
Above I high
See parameter group 5-3* for further description.
[10]
Out of speed range
[11]
Below speed low
See parameter group 5-3* for further description.
[12]
Above speed high
See parameter group 5-3* for further description.
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
See parameter group 5-3* for further description.
[17]
Mains out of range
See parameter group 5-3* for further description.
[18]
Reversing
See parameter group 5-3* for further description.
[19]
Warning
See parameter group 5-3* for further description.
[20]
Alarm (trip)
See parameter group 5-3* for further description.
[21]
Alarm (trip lock)
See parameter group 5-3* for further description.
[22]
Comparator 0
Use the result of comparator 0 in the logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the logic rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the logic rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the logic rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the logic rule.
[33]
Digital input DI18
Use the value of DI18 in the logic rule (High = TRUE).
[34]
Digital input DI19
Use the value of DI19 in the logic rule (High = TRUE).
[35]
Digital input DI27
Use the value of DI27 in the logic rule (High = TRUE).
[36]
Digital input DI29
Use the value of DI29 in the logic rule (High = TRUE).
[37]
Digital input DI32
Use the value of DI32 in the logic rule (High = TRUE).
[38]
Digital input DI33
Use the value of DI33 in the logic rule (High = TRUE).
[39]
Start command
This event is TRUE if the frequency converter is started by any means (either via digital input, field
bus or other).
[40]
Drive stopped
This event is TRUE if the frequency converter is stopped or coasted by any means (either via digital
input, fieldbus or other).
[41]
Reset Trip
This event is TRUE if the frequency converter is tripped (but not trip-locked) and the reset button
is pressed.