14-04 PWM Random
Option:
Function:
[0] *
Off
No change of the acoustic motor switching noise.
[1]
On
Transforms the acoustic motor switching noise from a clear ringing tone to a less noticeable ‘white’
noise. This is achieved by slightly and randomly altering the synchronism of the pulse width modu-
lated output phases.
2.13.3 14-1* Mains On/Off
Parameters for configuring mains failure monitoring and handling.
14-10 Mains Failure
Option:
Function:
Select the function at which the frequency converter must act, when the threshold set in par.
14-11
has been reached or a
Mains Failure Inverse
command is acti-
vated via one of the digital inputs (par. 5-1*).
[0] *
No function
The energy left in the capacitor bank will be used to "drive" the motor, but will be discharged.
[1]
Ctrl. ramp-down
The frequency converter will perform a controlled ramp-down. par.2-10
must be set
to
Off
[0].
[3]
Coasting
The inverter will turn off and the capacitor bank will back up the control card then ensuring a faster
restart when mains reconnected (at short power zags).
[4]
Kinetic back-up
The frequency converter will ride through by controlling speed for generative operation of the motor
utilizing the moment of inertia of the system as long as sufficient energy is present.
NB!
For best performance of controlled ramp-down and kinetic back-up par. 1-03
Torque Characteristics
should be set to
Compressor
[0]
or
Variable Torque
[1] (no automatic energy optimization should be active).
Illustration 2.2: Controlled Ramp-down - short mains failure. Ramping down to stop followed by ramping up to reference.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
135