2.9.3 8-1* Ctrl. Word Settings
Parameters for configuring the option control word profile.
8-10 Control Profile
Option:
Function:
Select the interpretation of the control and status words corresponding to the installed fieldbus.
Only the selections valid for the fieldbus installed in slot A will be visible in the LCP display.
[0] *
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
[0]
No function
[1] *
Profile Default
Function corresponds to the profile default selected in par.8-10
[2]
Alarm 68 Only
Only set in case of an Alarm 68.
[3]
Trip excl Alarm 68
Set in case of a trip, except if the trip is executed by an Alarm 68.
[16]
T37 DI status
The bit indicates the status of terminal 37.
“0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
2.9.4 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Option:
Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the control card.
[0] *
FC
Communication according to the FC Protocol as described in
RS-485 Installation and Set-up
.
[1]
FC MC
Same as
FC
[0] but to be used when downloading SW to the frequency converter or uploading dll
file (covering information regarding parameters available in the frequency converter and their inter-
dependencies) to Motion Control Tool MCT10.
[2]
Modbus RTU
Communication according to the Modbus RTU protocol.
[9]
FC option
8-31 Address
Range:
Function:
1. N/A*
[1. - 126. N/A]
Enter the address for the FC (standard) port.
Valid range: 1 - 126.
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
98
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2