0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled
No function
[1] *
Enabled
[Auto on] Key is enabled
[2]
Password
Avoid unauthorized start in Auto mode. If par.0-42
is included in the My
Personal Menu, then define the password in par.0-65
. Otherwise define
the password in par.0-60
0-43 [Reset] Key on LCP
Option:
Function:
[0]
Disabled
No function
[1] *
Enabled
[Reset] Key is enabled
[2]
Password
Avoid unauthorized resetting. If par.0-43
My Personal
Menu
, then define the password in par.0-65
. Otherwise define the pass-
word in par.0-60
2.2.7 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option:
Function:
[0] *
No copy
No function
[1]
All to LCP
Copies all parameters in all set-ups from the frequency converter memory to the LCP memory. For
service purposes it is recommended to copy all parameters to the LCP after commissioning.
[2]
All from LCP
Copies all parameters in all set-ups from the LCP memory to the frequency converter memory.
[3]
Size indep. from LCP
Copies only the parameters that are independent of the motor size. The latter selection can be used
to programme several frequency converters with the same function without disturbing motor data
which are already set.
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option:
Function:
[0] *
No copy
No function
[1]
Copy to set-up 1
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 1.
[2]
Copy to set-up 2
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 2.
[3]
Copy to set-up 3
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 3.
[4]
Copy to set-up 4
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
2.2.8 0-6* Password
Define password access to menus.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description