Troubleshooting/FAQs
9.2 Diagnosing with PDM
64
SONO 3500 CT
Operating Instructions, 07/2019, VI.SH.P2.02
Error
code
Error
Remedy/Cause
F 8
Pulse output B overflow
Pulse output exceeds 100 Hz or 50% duty cycle
F 9
Datalogger warning/alarm
Datalogger warning monitors whether actual con-
sumption on Totalizer 1 is on end of log interval or
above/below the limit settings.
The warning has no influence on the flowmetering.
Check data logger values and consumption limit
(via PDM parameter 602)
Errors "F 1" to "F 4" affect the performance of the meter and the flowmeter may stop
measuring.
Errors "F 1" and "F 2" disappear when the alarm condition is corrected.
Errors "F 5" to "F 9" are only warnings and do not affect the measurement, but they will
influence the outputs.
The error indications disappear when the alarm conditions are corrected and a reset via the
communication interface has been carried out.
Example
Error code "F 1 2" in the display indicates a combination of error codes "F 1" and "F 2".
Possible causes:
●
Empty pipe
●
Path 1 and path 2 cables defective
●
Path 1 and path 2 cables not connected
●
Transducers defective
9.2
Diagnosing with PDM
SIMATIC PDM is a suitable tool for diagnosing the device. You can use SIMATIC PDM to
read all parameters available in the transmitter to a table for analyzing offline, view
online/actual process values and online/actual diagnostic information.
Requirements
The following procedure must be completed before diagnosing:
●
Connection of Modbus interface via PC and IrDA, see Commissioning via PDM (Page 40)
●
Installation of PDM and transmitter PDM driver, see Installing EDD files (Page 41)
Содержание SONO 3500 CT
Страница 1: ...Ultrasonic Flowmeter Operating Instructions SONO 3500 CT 07 2019 Edition ...
Страница 2: ......
Страница 8: ...Table of contents 6 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 14: ...Introduction 1 5 Further Information 12 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 38: ...Electrical connection 5 5 Sealing of SONO 3500 CT 36 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 50: ...Commissioning 6 4 Commissioning via PDM 48 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 54: ...Functions 7 4 Hardware key 52 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 64: ...Service and maintenance 8 7 Battery disposal 62 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...