Commissioning
6.4 Commissioning via PDM
SONO 3500 CT
Operating Instructions, 07/2019, VI.SH.P2.02
45
6.4.6
Output A, terminals 56/57:
Pulse rate can be seen on transmitter side label (system nameplate).
The settings are depending on the ordering. The following table shows the recommended
pulse output settings (pulse width 5 ms), which can be adapted to heat calculator INFOCAL
9
.
DN
Pulse setting (liter/pulse)
100
2.5
125
2.5
150
2.5
200
10
250
10
300
10
350
10
400
50
500
5
0
600
100
700
100
800
100
900
100
1000
100
1200
100
Note
For use with a energy calculator the pulse value must correspond to pulse setting of energy
calculator.
6.4.7
Output B, terminals 66/67:
The output B setting must be selected according to application specific requirements (Default
setting = Alarm).
Preset to alarm indication:
Example: If track 1 is not measuring, a "triangle" alert appears on display. Failure code "F1"
appears in display menu 4, and relay output terminals switch to "off".
Содержание SONO 3500 CT
Страница 1: ...Ultrasonic Flowmeter Operating Instructions SONO 3500 CT 07 2019 Edition ...
Страница 2: ......
Страница 8: ...Table of contents 6 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 14: ...Introduction 1 5 Further Information 12 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 38: ...Electrical connection 5 5 Sealing of SONO 3500 CT 36 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 50: ...Commissioning 6 4 Commissioning via PDM 48 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 54: ...Functions 7 4 Hardware key 52 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 64: ...Service and maintenance 8 7 Battery disposal 62 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...