Installation in large pipes
The flowmeter can be installed between two reducers as shown. At 8° reducing angles the
below pressure drop curve applies.
Delta-P example:
A water flow velocity of 3 m/s (V) in a sensor with a diameter reduction from DN 200 to DN
100 (D
1
/D
2
= 0.5) gives a pressure drop of 9 mbar.
L2: Min. 10 x pipe diameter
4.2.3
Insulation
Both versions can be insulated.
We always recommend insulation of sensor in the compact or remote version. For compact
versions the insulation can prevent heat transfer to transmitter.
4.3
Transmitter installation (compact/remote versions)
The transmitter is packed separately - ready for plug-in into base part.
There are two mounting versions of the transmitter (as shown in figures below):
●
remote transmitter
●
compact transmitter
Содержание SONO 3500 CT
Страница 1: ...Ultrasonic Flowmeter Operating Instructions SONO 3500 CT 07 2019 Edition ...
Страница 2: ......
Страница 8: ...Table of contents 6 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 14: ...Introduction 1 5 Further Information 12 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 38: ...Electrical connection 5 5 Sealing of SONO 3500 CT 36 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 50: ...Commissioning 6 4 Commissioning via PDM 48 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 54: ...Functions 7 4 Hardware key 52 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 64: ...Service and maintenance 8 7 Battery disposal 62 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...