Installing the Scanner 2000 

Direct Mount 

To install the Scanner 2000 microEFM using a direct mount to 

an orifice or cone meter run, perform the following steps: 

1.  Determine the best location for the Scanner 2000.  

a.  For horizontal meter runs, locate process connections at 

the top of the line, and mount the Scanner 2000 above 

the pressure connections at the pipe. 

b.  For vertical meter runs, make sure pipeline flow is up-

ward. 

2.  Locate the H and L markings on the Scanner 2000 transmit-

ter designating high-pressure and low-pressure ports, and 

connect a valve manifold (if desired) to the transmitter. 

3.  Connect the orifice flanges to the Scanner 2000/manifold 

assembly, matching the upstream tap to the high-pressure 

manifold port and the downstream tap to the low-pressure 

manifold port. 

ADJUSTABLE HEAD DESIGN.

When the sensor is oriented ap-

propriately for pressure connec-

tions, the position of the Scanner 

display may need to be adjusted. 

To change the orientation of the 

head, loosen the set screw in the 

MVT adapter, rotate the head 

no more than 180 degrees and 

tighten the set screw. 

Remote Mount 

To install the Scanner 2000 microEFM remotely from the 

flow run,  perform the following steps:

1.  Mount the Scanner to a flat, vertical surface, or bolt 

to a 2-in. pipe using optional pole-mount hardware. 

2.  Install process tubing between the orifice run and 

the manifold, making sure that the  upstream pres-

sure tap is connected to the high-pressure manifold 

port and the downstream pressure tap is connected 

to the low-pressure manifold port.  Slope all piping 

at least 1-inch per linear foot to avoid trapping 

liquid.

3.  Use a suitable compound or tape on all threaded 

process connections. 

4.  Position all shutoff and bypass valves so they are  

accessible from the front of the instrument. 

5.  Check the manifold for leaks.

POLE-MOUNT OPTION.

An optional pole mount kit 

(Part No. 9A-30028004)  

allows the Scanner 2000 to 

be mounted to a 2-in.  

vertical or horizontal pipe. 

The kit includes a mounting 

bracket, two U-bolts and 

screws for connecting the 

bracket to the Scanner 2000 

enclosure.

Set screw

Flow

H L

H L

Summary of Contents for NUFLO Scanner 2000 microEFM

Page 1: ...ay need to be adjusted To change the orientation of the head loosen the set screw in the MVT adapter rotate the head no more than 180 degrees and tighten the set screw Remote Mount To install the Scan...

Page 2: ...UP B A TB1 TFM1 I R R I 2 3 4 5 6 1 BLACK RED DIGITAL OUTPUT 13 14 Leave this end of shield disconnected POWER SUPPLY 5 to 30 VDC Resistor may be included in pulse readout device Size the resistor to...

Page 3: ...digit to the left Repeat using UP ARROW LOG and LEFT ARROW DISPLAY to enter all remaining digits Press ENTER SAVE Keypad Configuration Controls Remove the instrument cover to access the keypad Each of...

Page 4: ...is the control center for the Scanner 2000 and provides quick and easy access to the most commonly performed tasks From this screen the user can view real time totals and flow rates input data and sy...

Page 5: ...o perform Then select the parameter you want to calibrate 2 Click Acquire Point to enter a new calibration point and enter the applied calibration value at the prompt Or click Load Calibration From to...

Page 6: ...od used Click Change Task to select a new maintenance task 1 Select the task you want to perform 3 Click Save Changes to save the new parameters to memory 2 Enter new parameters in the fields provided...

Page 7: ...to specify plate parameters 9 Enter base conditions specific to the location 10 Click Change Composition to specify the gas composition Percentages must total 100 8 Specify pipe parameters 11 Click O...

Page 8: ...screen Download Screens Part No 9A 30165024 Rev 03 To download data simply press the Download button and select the range and type of files to be downloaded Daily and interval logs can be viewed or p...

Reviews: