The image shows the M12 to RJ45 Ethernet cable connecting the Ouster Interface Box directly to the
XM100 controller.
Disconnect the Ethernet Output Parameters
After connecting the Ouster LiDAR hardware, adding the Ouster LiDAR compliance block, then
configuring the parameters, disconnect the Ethernet output parameters from the controller template.
When the Ouster LiDAR hardware is directly connected to a controller, the Ouster LiDAR compliance
block provides the network parameters required for communication between the controller and LiDAR.
Disconnect the parameters in the Ethernet output in the controller template to prevent conflicts during
run time.
1. From the top of the application, enter the Outputs page, then the Ethernet page. Do not open the
USBEthernet page.
2. Delete the wire bus segment between the parameters and the output bus.
The following image highlights the wire bus segment to be deleted.
User Manual
Ouster LiDAR
Configure One LiDAR
20 |
©
Danfoss | March 2023
AQ404281942428en-000103