Illustration 5.49:
Step 8
: Press the [Off] button to stop the motor again.
Illustration 5.50:
Step 9
: Change two motor wires if the desired rotation of
direction is not achieved.
Remove mains power from the frequency converter before changing motor wires.
5.1.27 Switches S201, S202 and S801
Switches S201 (Al 53) and S202 (Al 54) are used to select a current (0-20
mA) or a voltage (0 to 10 V) configuration of the analog input terminals
53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination on the RS-485
port (terminals 68 and 69).
Please note that the switches may be covered by an option, if fitted.
Default setting:
S201 (AI 53) = OFF (voltage input)
S202 (AI 54) = OFF (voltage input)
S801 (Bus termination) = OFF
Illustration 5.51: Switches location.
5 Electrical Installation
Automation VT Drive FC322
Instruction Manual
52
MG.20.U1.22
5