22-33 Low Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 50% level.
The function is used for storing values needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-37 High Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-39 High Speed Power [HP]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-40 Minimum Run Time
Range:
Function:
60 s*
[0 - 600 s]
Set the desired minimum running time for the motor after a start command (digital input or Bus)
before entering Sleep Mode.
8 How to Programme the Frequency Converter
Automation VT Drive FC322
Instruction Manual
110
MG.20.U1.22
8
Содержание FC322 Series
Страница 6: ...2 Safety Automation VT Drive FC322 Instruction Manual 6 MG 20 U1 22 2 ...
Страница 14: ...4 Mechanical Installation Automation VT Drive FC322 Instruction Manual 14 MG 20 U1 22 4 ...
Страница 103: ...Automation VT Drive FC322 Instruction Manual 8 How to Programme the Frequency Converter MG 20 U1 22 103 8 ...
Страница 154: ...9 Troubleshooting Automation VT Drive FC322 Instruction Manual 154 MG 20 U1 22 9 ...
Страница 163: ...10 Specifications Automation VT Drive FC322 Instruction Manual 10 Specifications MG 20 U1 22 163 10 ...