Terminal number
Terminal description
Parameter number
Factory default
1+2+3
Terminal 1+2+3-Relay1
5-40
No operation
4+5+6
Terminal 4+5+6-Relay2
5-40
No operation
12
Terminal 12 Supply
-
+24 V DC
13
Terminal 13 Supply
-
+24 V DC
18
Terminal 18 Digital Input
5-10
Start
19
Terminal 19 Digital Input
5-11
No operation
20
Terminal 20
-
Common
27
Terminal 27 Digital Input/Output
5-12/5-30
Coast inverse
29
Terminal 29 Digital Input/Output
5-13/5-31
Jog
32
Terminal 32 Digital Input
5-14
No operation
33
Terminal 33 Digital Input
5-15
No operation
37
Terminal 37 Digital Input
-
Safe Stop
42
Terminal 42 Analog Output
6-50
Speed 0-HighLim
53
Terminal 53 Analog Input
3-15/6-1*/20-0*
Reference
54
Terminal 54 Analog Input
3-15/6-2*/20-0*
Feedback
Table 5.5: Terminal connections
Very long control cables and analog signals may, in rare cases and depending on installation, result in 50/60 Hz earth loops due to noise from mains
supply cables.
If this occurs, break the screen or insert a 100 nF capacitor between screen and chassis.
NB!
The common of digital / analog inputs and outputs should be connected to separate common terminals 20, 39, and 55. This will avoid
ground current interference among groups. For example, it avoids switching on digital inputs disturbing analog inputs.
NB!
Control cables must be screened/armoured.
5.1.26 How to Test Motor and Direction of Rotation
Note that unintended motor start can occur, ensure no personnel or equipment is in danger!
Illustration 5.42:
Step 1
: First remove the insulation on both ends of a 50 to
70 mm piece of wire.
5 Electrical Installation
Automation VT Drive FC322
Instruction Manual
50
MG.20.U1.22
5
Содержание FC322 Series
Страница 6: ...2 Safety Automation VT Drive FC322 Instruction Manual 6 MG 20 U1 22 2 ...
Страница 14: ...4 Mechanical Installation Automation VT Drive FC322 Instruction Manual 14 MG 20 U1 22 4 ...
Страница 103: ...Automation VT Drive FC322 Instruction Manual 8 How to Programme the Frequency Converter MG 20 U1 22 103 8 ...
Страница 154: ...9 Troubleshooting Automation VT Drive FC322 Instruction Manual 154 MG 20 U1 22 9 ...
Страница 163: ...10 Specifications Automation VT Drive FC322 Instruction Manual 10 Specifications MG 20 U1 22 163 10 ...