9 Troubleshooting
9.1 Alarms and Warnings
A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display.
A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued. Warning messages
may be critical, but are not necessarily so.
In the event of an alarm, the frequency converter will have tripped. Alarms must be reset to restart operation once their cause has been rectified.
This may be done in four ways:
1.
By using the [RESET] control button on the LCP control panel.
2.
Via a digital input with the “Reset” function.
3.
Via serial communication/optional fieldbus.
4.
By resetting automatically using the [Auto Reset] function, which is a default setting for Automation VT Drive. See par. 14-20
Reset Mode
in
Automation VT Drive Programming Guide.
NB!
After a manual reset using the [RESET] button on the , the [AUTO ON] or [HAND ON] button must be pressed to restart the motor.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also table on following page).
Alarms that are trip-locked offer additional protection, means that the mains supply must be switched off before the alarm can be reset. After being
switched back on, the frequency converter is no longer blocked and may be reset as described above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in par. 14-20
Reset Mode
(Warning: automatic wake-up is possible!)
If a warning and alarm is marked against a code in the table on the following page, this means that either a warning occurs before an alarm, or it can
be specified whether it is a warning or an alarm that is to be displayed for a given fault.
This is possible, for instance, in par. 1-90
Motor Thermal Protection
. After an alarm or trip, the motor carries on coasting, and the alarm and warning
flash on the frequency converter. Once the problem has been rectified, only the alarm continues flashing.
Automation VT Drive FC322
Instruction Manual
9 Troubleshooting
MG.20.U1.22
155
9
Содержание FC322 Series
Страница 6: ...2 Safety Automation VT Drive FC322 Instruction Manual 6 MG 20 U1 22 2 ...
Страница 14: ...4 Mechanical Installation Automation VT Drive FC322 Instruction Manual 14 MG 20 U1 22 4 ...
Страница 103: ...Automation VT Drive FC322 Instruction Manual 8 How to Programme the Frequency Converter MG 20 U1 22 103 8 ...
Страница 154: ...9 Troubleshooting Automation VT Drive FC322 Instruction Manual 154 MG 20 U1 22 9 ...
Страница 163: ...10 Specifications Automation VT Drive FC322 Instruction Manual 10 Specifications MG 20 U1 22 163 10 ...