22-41 Minimum Sleep Time
Range:
Function:
30 s*
[0 - 600 s]
Set the desired Minimum Time for staying in Sleep Mode. This will override any wake up conditions.
22-42 Wake-up Speed [RPM]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Only to be used if par. 1-00
is set for Open Loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
22-43 Wake-up Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
, has been set for Hz (parameter not visible if RPM selected).
Only to be used if par. 1-00
, is set for Open Loop and speed reference is applied
by an external controller controlling the pressure.
Set the reference speed at which the Sleep Mode should be cancelled.
22-44 Wake-up Ref./FB Difference
Range:
Function:
10%*
[0-100%]
Only to be used if par. 1-00,
Configuration Mode
, is set for Closed Loop and the integrated PI
controller is used for controlling the pressure.
Set the pressure drop allowed in percentage of set point for the pressure (Pset) before cancelling
the Sleep Mode.
NB!
If used in application where the integrated PI controller is set for inverse control
in par. 20-71,
PID, Normal/Inverse Control
, the value set in par. 22-44 will au-
tomatically be added.
22-45 Setpoint Boost
Range:
Function:
0 %*
[-100 - 100 %]
Only to be used if par. 1-00
, is set for Closed Loop and the integrated PI con-
troller is used. In systems with e.g. constant pressure control, it is advantageous to increase the
system pressure before the motor is stopped. This will extend the time in which the motor is stopped
and help to avoid frequent start/stop.
Set the desired over pressure/temperature in percentage of set point for the pressure (Pset)/tem-
perature before entering the Sleep Mode.
If setting for 5%, the boost pressure will be Pset*1.05. The negative values can be used for e.g.
cooling tower control where a negative change is needed.
22-46 Maximum Boost Time
Range:
Function:
60 s*
[0 - 600 s]
Only to be used if par. 1-00
is set for Closed Loop and the integrated PI controller
is used for controlling the pressure.
Set the maximum time for which boost mode will be allowed. If the set time is exceeded, Sleep
Mode will be entered, not waiting for the set boost pressure to be reached.
Automation VT Drive FC322
Instruction Manual
8 How to Programme the Frequency Converter
MG.20.U1.22
111
8
Содержание FC322 Series
Страница 6: ...2 Safety Automation VT Drive FC322 Instruction Manual 6 MG 20 U1 22 2 ...
Страница 14: ...4 Mechanical Installation Automation VT Drive FC322 Instruction Manual 14 MG 20 U1 22 4 ...
Страница 103: ...Automation VT Drive FC322 Instruction Manual 8 How to Programme the Frequency Converter MG 20 U1 22 103 8 ...
Страница 154: ...9 Troubleshooting Automation VT Drive FC322 Instruction Manual 154 MG 20 U1 22 9 ...
Страница 163: ...10 Specifications Automation VT Drive FC322 Instruction Manual 10 Specifications MG 20 U1 22 163 10 ...