8.2.11 23-0* Timed Actions
Use
Timed Actions
for actions needing to be performed on a daily or weekly basis, e.g. different references for working hours / non-working hours. Up
to 10 Timed Actions can be programmed in the frequency converter. The Timed Action number is selected from the list when entering parameter group
23-0* from the . par. 23-00
then refer to the selected Timed Action number. Each Timed Action is divided into an ON
time and an OFF time, in which two different actions may be performed.
The actions programmed in Timed Actions are merged with corresponding actions from digital inputs, control work via bus and Smart Logic Controller,
according to merge rules set up in 8-5*, Digital/Bus.
NB!
The clock (parameter group 0-7*) must be correctly programmed for Timed Actions to function correctly.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
NB!
The PC-based Configuration Tool MCT 10 comprise a special guide for easy programming of Timed Actions.
23-00 ON Time
Array [10]
Range:
Function:
Application
dependent*
[Application dependant]
Sets the ON time for the Timed Action.
NB!
The frequency converter has no back up of the clock function and the set date/
time will reset to default (2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed. In par. 0-79
Clock Fault
it is possible
to program for a Warning in case clock has not been set properly, e.g. after a
power down.
23-01 ON Action
Arra [10]
Option:
Function:
Select the action during ON Time. See par. 13-52
SL Controller Action
for descriptions of the options.
[0] *
Disabled
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset ref 0
[11]
Select preset ref 1
8 How to Programme the Frequency Converter
Automation VT Drive FC322
Instruction Manual
116
MG.20.U1.22
8
Содержание FC322 Series
Страница 6: ...2 Safety Automation VT Drive FC322 Instruction Manual 6 MG 20 U1 22 2 ...
Страница 14: ...4 Mechanical Installation Automation VT Drive FC322 Instruction Manual 14 MG 20 U1 22 4 ...
Страница 103: ...Automation VT Drive FC322 Instruction Manual 8 How to Programme the Frequency Converter MG 20 U1 22 103 8 ...
Страница 154: ...9 Troubleshooting Automation VT Drive FC322 Instruction Manual 154 MG 20 U1 22 9 ...
Страница 163: ...10 Specifications Automation VT Drive FC322 Instruction Manual 10 Specifications MG 20 U1 22 163 10 ...