Precautions for New Refrigerant (R-410A)
SiUS34-801A_b
538
Precautions for New Refrigerant (R-410A)
1.2
Service Tools
R-410A is used under higher working pressure, compared to previous refrigerants (R-22,R-407C).
The refrigerating machine oil has been changed from Suniso oil to Ether oil, and if oil mixing occurs,
sludge builds in the refrigerants and causes other problems. Therefore, gauge manifolds and
charge hoses with a previous refrigerant (R-22,R-407C) cannot be used for products with new
refrigerants.
Be sure to use dedicated tools and devices.
Tool compatibility
For the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of charge
hose.
Copper tube material and thickness
* O: Soft (Annealed)
H: Hard (Drawn)
Tool
Compatibility
Reasons for change
HFC
HCFC
R-410A
R-407C
R-22
Gauge manifold
Charge hose
2
Do not use the same tools for R-22 and
R-410A.
2
Thread specification differs for R-410A
and R-407C.
Gas detector
2
The same tool can be used for HFCs.
Vacuum pump
(pump with reverse flow
preventive function)
2
To use existing pump for HFCs,
vacuum pump adaptor must be
installed.
Weighting instrument
Flaring tool (Clutch type)
2
For R-410A, flare gauge is necessary.
Torque wrench
2
Torque-up for 1/2 and 5/8
Pipe cutter
Pipe expander
Pipe bender
Pipe assembling oil
2
Due to refrigerating machine oil
change. (No Suniso oil can be used.)
Refrigerant recovery
device
Check your recovery device.
Refrigerant piping
See the chart below.
2
Only
φ
19.1 is changed to 1/2H material
while the previous material is "O".
Pipe size
[in]
φ
1/4”
φ
3/
8
”
φ
1/2”
φ
5/
8
“
φ
3/4”
φ
7/
8
”
φ1.0
”
φ
1-1/
8
”
φ
1-5/16”
φ
1-1/2”
φ
1-3/4”
Material
O
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Material
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Thickness
[in]
0.
8
/32
0.
8
/32
0.
8
/32
1.0/32
1.0/32
1.0/32
1.0/32
1.0/32
1.2/32
1.4/32
1.6/32
Thickness
[in]
0.
8
/32
0.
8
/32
0.
8
/32
1.0/32
1.0/32
1.0/32
1.0/32
1.0/32
1.1/32
1.4/32
1.6/32
R-407C
R-410A
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...