SiUS34-801A_b
Field Setting
VRVIII R-410A Heat Recovery 60Hz
241
12.Field Setting
12.1 Field Setting from Outdoor Unit
12.1.1 Field Setting from Outdoor Unit
List of Field Setting Items
This following section indicates the list of field setting items. For the lists of dip switch contents,
Setting mode 1
, and
Setting mode 2
, refer to information in tables shown on the following page
onward.
For setting items of (*1), refer to detailed information provided on page 249 onward.
Setting item
Content and objective of setting
Overview of setting procedure
Reference
page
F
u
nct
ion
se
tti
n
g
2
Setting of low
noise
operation
(*1)
A. Use external input to step down the upper
limit of the fan (factory set to Step 8),
providing low noise level.
(1) Mode 1: Step 5 or lower
(2) Mode 2: Step 4 or lower
(3) Mode 3: Step 3 or lower
Use the
External control adaptor for
outdoor unit
.
Set to
External control adaptor for
outdoor unit
with No. 12 of
Setting
mode 2
and select the mode with No.
25.
If necessary, set the
Capacity priority
setting
to ON with No. 29.
B. The low noise operation aforementioned is
enabled in nighttime automatic low noise
operation mode.
Start time: Possible to select in the range of
20:00 to 24:00 hours.
End time: Possible to select in the range of
06:00 to 08:00 hours.
Use the said time as a guide since the start
time and the end time are estimated
according to outdoor temperatures.
Make this setting while in
Setting mode
2
.
Select a mode with No. 22 of
Setting
mode 2
.
Select the start time with No. 26 and the
end time with No. 27.
If necessary, set the
Capacity priority
setting
to ON with No. 29.
3
Setting of
demand
operation
(*1)
Used to place limits on the compressor
operating frequency to control the upper
limit of power consumption.
(1) Mode 1 of Demand 1: 60% or less of
rating
(2) Mode 2 of Demand 1: 70% or less of
rating
(3) Mode 3 of Demand 1: 80% or less of
rating
(4) Demand 2: 40% or less of rating
For setting with the use of an
External
Control Adapter
:
Set the system to
External control
adaptor for outdoor unit
with No. 12 of
Setting mode 2
and select the mode
with No. 30.
For setting only in
Setting mode 2
:
Set the system to Normal demand mode
with No. 32 of
Setting mode 2
and
select the mode with No. 30.
4
Setting of
AirNet
address
Used to make address setting with AirNet
connected.
Set the AirNet to an intended address
using binary numbers with No. 13 of "
Setting mode 2
.
6
Setting of
high static
pressure
Make this setting to operate a system with
diffuser duct while in high static pressure
mode. Use this setting mode when shields
are installed on upper floors or balconies.
* In order to mount the diffuser duct, remove
the cover from the outdoor unit fan.
Set No. 18 of
Setting mode 2
to ON.
7
Prevention of
bleed heating
operation by
heating
thermostat
OFF unit or
non-heating-
operation
unit
Make this setting to prevent a rise in room
temperature due to bleed heating capacity
generated by heating thermostat OFF unit
or non-heating-operation unit while in
heating operation.
Set the Setting item No. 41 of
Setting
mode 2
to heating thermostat OFF unit
or non-heating-operation unit.
(Overseas unit: Default set to
ON
)
8
Setting of BS
Cool-Heat
selection
control time
Make this setting to shorten the BS Cool-
Heat selection control time.
Set the Setting item No. 42 of
Setting
mode 2
to
ON
.
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...