SiUS34-801A_b
Test Operation
VRVIII R-410A Heat Recovery 60Hz
231
MODE button (BS1).
[Automatic refrigerant charging operation procedure]
NOTE:
The LED signals represent the following:
h
: OFF
i
: ON
j
: Blinking
∗
: OFF, ON or Blinking
(1) Open the liquid pipe, suction gas pipe and HP/LP gas pipe shutoff valves. (The valve A~C must
be closed. See figure 31.)
(2) • Close the Electrical Componets Box (1) lid and all front panels except on the Electrical
Componets Box (1) side. (*1) Turn on the power to the outdoor unit and all connected BS,
indoor units. (*2)
• After H2P stops blinking (about 12 minutes after turning on the power), check that H2P is OFF.
If H2P is ON, check the malfunction code in the remote controller of indoor unit and correct the
malfunction in accordance with [
Remote controller display malfunction code
] in chapter 11-
2-2.
(3) Check the LED. And push the MODE button (BS1) once if the LED displays is not as shown in
the following diagram:
H1P H2P H3P H4P H5P H6P H7P
h
h
i
h
h
h
h
Measuring device
R-410A tank (with siphon)
Charge hose
Equalizer pipe shutoff valve
Valve C
Outside unit A Outside unit B
Valve A
To BS,
indoor unit
Valve B
HP/LP gas pipe shutoff valve
Suction pipe shutoff valve
Liquid pipe shutoff valve
Refrigerant charge port
Valve A
The refrigerant will be charged about
66 lb in one hour at outdoor temp.
86˚FDB (26 lb at 32˚FDB).
(According to outdoor temp. or the
refrigerant amount in the tank, the
charging rate may speed up). If you
need to speed up in case of multi
system, connect the refrigerant tanks
to each outside unit.
: Field pipings
: Refrigerant flow when charging
)
(
: Shutoff valve
: Service port
figure 31
Measuring device
R-410A tank (with siphon)
Charge hose
Outside unit
To BS,
indoor unit
Valve C
Refrigerant charge port
HP/LP gas pipe shutoff valve
Suction pipe shutoff valve
Liquid pipe shutoff valve
Valve B
Valve A
(
)
: Field pipings
: Refrigerant flow when charging
: Shutoff valve
: Service port
REYQ72~120PYDN
REYQ72~144PTJU
REMQ72~120PYDN
REMQ72~120PTJU
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...