SiUS34-801A_b
Field Settings
VRVIII R-410A Heat Pump 60Hz
107
the low-noise operation input terminal on the terminal block (X1M). (Refer to the figure shown
below.)
2. While in
[
Setting mode 2
]
, set the setting condition for set item No. 12 (Setting of external low
noise/demand operation) to "YES".
3. If necessary, while in
[
Setting mode 2
]
, select the setting condition (i.e., L
evel
1", "
Level
2", or
"Level 3") for set item No. 25 (Setting of external low noise level).
4. If necessary, while in
[
Setting mode 2
]
, set the setting condition for the set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the low noise
operation command will be ignored to put the system into normal operation mode.)
B. When the low noise operation is carried out automatically at night (The external control
adaptor for outdoor unit is not required)
1. While in
[
Setting mode 2
]
, select the setting condition (i.e., "
Level
1", "
Level
2", or "
Level
3") for
set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in
[
Setting mode 2
]
, select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in
[
Setting mode 2
]
, select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in
[
Setting mode 2
]
, set the setting condition for set item No. 29 (Setting of
capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the system
will be put into normal operation mode even during nighttime.)
To other external control adaptor
for outdoor unit
Host computer monitor panel or demand controller
Demand
2
P
Outside
wiring
indicated by
dotted line.
3
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
F1
F2
N
1
C
X1M
Low
noise
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...