Troubleshooting by Remote Controller
SiUS34-801A_b
330
Troubleshooting
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Indoor Unit
A0
9
9
9
Error of external protection device
338
A1
9
9
9
PC board defect, E
2
PROM defect
A3
9
9
9
Malfunction of drain level control system (S1L)
A6
9
9
9
Fan motor (M1F) lock, overload
342
344
345
A7
8
7
9
Malfunction of swing flap motor (M1S)
A9
9
9
9
Malfunction of moving part of electronic expansion
valve / Dust clogging
346
350
AF
8
7
9
Drain level about limit
AH
8
7
9
Malfunction of air filter maintenance
—
AJ
9
9
9
Malfunction of capacity setting
C4
9
9
9
Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
C5
9
9
9
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
354
C9
9
9
9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
CJ
8
8
8
Malfunction of thermostat sensor in remote controller
Outdoor Unit
E1
9
9
9
PC board defect
E2
9
9
9
Detection of ground leakage by leak detection PC
board assembly
358
E3
9
9
9
Actuation of high pressure switch
360
E4
9
9
9
Actuation of low pressure sensor
E5
9
9
9
Compressor motor lock
364
E6
9
9
9
Standard compressor lock or over current
E7
9
9
9
Malfunction of outdoor unit fan motor
367
E9
9
9
9
Malfunction of moving part of electronic expansion
valve (Y1E, Y2E, Y3E)
F3
9
9
9
Abnormal discharge pipe temperature
F6
9
9
9
Refrigerant overcharged
F9
9
9
9
Malfunction of BS unit electronic expansion valve
—
H7
9
9
9
Abnormal outdoor fan motor signal
H9
9
9
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
J2
9
9
9
Current sensor malfunction
J3
9
9
9
Malfunction of discharge pipe thermistor (R31, 32T,
33T) (loose connection, disconnection, short circuit,
failure)
384
J4
9
9
9
Malfunction of temperature sensor for heat exchanger
gas (R2T)
385
J5
9
9
9
Malfunction of thermistor (R8T) for suction pipe (loose
connection, disconnection, short circuit, failure)
J6
9
9
9
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit, failure)
J7
9
9
9
Malfunction of receiver outlet liquid pipe thermistor (R6T),
(9T)
J8
9
9
9
Malfunction of liquid pipe thermistor 2 (R7T)
J9
9
9
9
Malfunction of subcooling heat exchanger gas pipe
thermistor (R5T)
JA
9
9
9
Malfunction of high pressure sensor
JC
9
9
9
Malfunction of low pressure sensor
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...