Field Setting
SiUS34-801A_b
258
VRVIII R-410A Heat Recovery 60Hz
Setting of Demand Operation
By connecting the external contact input to the demand input of the outdoor unit external control
adaptor (optional), the power consumption of unit operation can be saved by suppressing the
compressor operating condition.
A. When the demand operation is carried out by external instructions (with the use of the
external control adaptor for outdoor unit).
1. Connect the external adaptor of the outdoor unit, and then connect the external input wiring to
the low-noise operation input terminal on the terminal block (X1M). (Refer to the figure shown
below.)
2. While in
Setting mode 2
, set the setting condition for set item No. 12 (Setting of external low
noise/demand operation) to
YES
.
3. If necessary, while in
Setting mode 2
, select the set item No. 30 (Setting of Demand 1 level)
and then set the setting condition to targeted mode.
B. When the Normal demand operation is carried out. (Use of the external control adapter
for outdoor unit is not required.)
1. While in
Setting mode 2
, make setting of the set item No. 32 (Setting of constant demand) to
ON
.
2. While in
Setting mode 2
, select the set item No. 30 (Setting of Demand 1 level) and then set
the setting condition to targeted mode.
Description of setting
Setting procedure
Setting
item
Condition
Description
External control
adaptor
Outdoor unit PC board
Demand 1
Level 1
Operate with power
of approx. 60% or
less of the rating.
Short-circuit
between "1" and [
C
]
of the terminal block
(TeS1).
Set the setting item No. 32 to
Demand 1
and the setting item No.
30 to
Level 1
.
Level 2
Operate with power
of approx. 70% or
less of the rating.
Set the setting item No. 32 to
Demand 1
and the setting item
No. 30 to
Level 2
.
Level 3
Operate with power
of approx. 80% or
less of the rating.
Set the setting item No. 32 to
Demand 1
and the setting item
No. 30 to
Level 3
.
Demand 2
–
Operate with power
of approx. 40% or
less of the rating.
Short-circuit
between [
2
]and [
C
].
Set the setting item No. 32 to
Demand 2
.
Demand 3
–
Operate with forced
thermostat OFF
Short-circuit
between [
3
] and [
C
].
–
To other external control adaptor
for outdoor unit
Demand
2
P
Outside
wiring
indicated by
dotted line.
3
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
F1
F2
N
1
C
Low
noise
X1M
Host computer monitor panel or demand controller
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...