SiUS34-801A_b
Special Control
VRVIII R-410A Heat Recovery 60Hz
203
7.4
Defrost Operation
[Start conditions]
Referring to the following conditions, start defrost operation.
• When there is a decrease in the coefficient of heat transfer of outdoor unit heat exchanger
• When there is a drop in the temperature of outdoor unit heat exchanger outlet (Tb)
• When the low pressure stays low for a certain amount of time (2 hours minimum)
Furthermore, the thermal conductivity of outdoor unit heat exchanger is calculated by Tc, Te, and compressor loads.
Cooling indoor unit actuator
Oil return operation
Fan
Thermo ON unit
Remote controller setting
Unit not in operation
OFF
Thermo OFF unit
Remote controller setting
Motorized valve
Thermo ON unit
Normal opening degree
Unit not in operation
192pls
Thermo OFF unit
Normal opening degree for forced thermostat ON
Heating indoor unit actuator
Oil return operation
Fan
Thermo ON unit
Remote controller setting
Unit not in operation
OFF
Thermo OFF unit
LL
Motorized valve
Thermo ON unit
Normal opening degree
Unit not in operation
224 pls
Thermo OFF unit
Normal opening degree for forced thermostat ON
Cooling BS unit actuator
Elect. symbol
Oil return operation
Electronic expansion valve (EVH)
Y4E
0pls
Electronic expansion valve (EVL)
Y5E
760pls
Electronic expansion valve (EVHS)
Y2E
0pls (60pls when Pc_max>413.25psi)
Electronic expansion valve (EVLS)
Y3E
480pls
Electronic expansion valve (EVSC)
Y1E
PI control
Heating BS unit actuator
Elect. symbol
Oil return operation
Electronic expansion valve (EVH)
Y4E
760pls
Electronic expansion valve (EVL)
Y5E
0pls
Electronic expansion valve (EVHS)
Y2E
60pls
Electronic expansion valve (EVLS)
Y3E
0pls (60pls when Pc_max>413.25psi)
Electronic expansion valve (EVSC)
Y1E
0pls (PI control at simultaneous cooling / heating
operation)
Defrosting outdoor unit actuator
Symbol
Elect.
symbol
Defrost operation
Operation after defrost
REYQ
REMQ
Compressor 1
—
M1C M1C REYQ72·96·120·144P: 232Hz+ON
REMQ72P: 210Hz
REMQ96·120P: 210Hz+ON
REYQ72·96·120·144P: upper limit
124Hz(STD Holds)
REMQ72P: 210Hz
REMQ96·120P: 210Hz+ON
Compressor 2
M2C M2C
Outdoor unit fan 1
—
M1F M1F
Outdoor unit fan 2
M2F M2F
Four-way valve (for heat changer
selection)
20SA
Y2S
Y9S
Y3S OFF
OFF
Four-way valve (for high- and low-
pressure gas pipe selection)
20SB Y8S Y2S Holds
Holds
Electronic expansion valve (main)
EVM
Y1E
Y3E
Y1E 1375pls
0pls
&
Pcmax>355.25psi
Pcmax>440.8psi
Pcmax<342.2psi
Pcmax<427.75psi
FANSTEP4
FANSTEP6
OFF
Pcmax>355.25psi
Pcmax>440.8psi
Pcmax<342.2psi
Pcmax<427.75psi
FANSTEP4
FANSTEP6
OFF
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...