Test Operation
SiUS34-801A_b
86
VRVIII R-410A Heat Pump 60Hz
(4) Push the TEST button (BS4) once. (The LED displays will change as shown below.)
(5) Hold the TEST button (BS4) down for 5 seconds or more.
(The LED displays will change as shown below and fan of outside unit will start rotation.)
(6) When the compressor start working and the LED displays change any state in below (*3), go to
In case of cooling mode
or
In case of heating mode
in accordance with the LED displays.
In case of cooling mode
(7) Push the TEST button (BS4) once within 5 minutes after procedure (5) (*4) and close all front
panels (*5).
After that, open valve A immediately (See figure 31) (*6) and watch the remote controller display
of indoor unit.
(8) If the remote controller display shows [
PE
] code (*7), ready to close valve A.
And go to procedure (9).
If the remote controller display shows other code, close valve A immediately and refer to
[Remote controller cooling mode malfunction code].
Beware of the fan running when opening the front panel.
The fan may continue rotation after the system stops operating.
(9) When the compressor stops working (the fan may continue rotation), close valve A immediately
(*8).
Check that the LED displays are as below and the remote controller display shows [
P9
] code.
After checking, push the MODE button (BS1) once and the charging is complete.
In case of heating mode
(7) Push the TEST button (BS4) once within 5 minutes after procedure (5) (*4) and close all front
panels.
After that, open valve A immediately (See figure 31) (*6) and check the charged amount with a
measuring device.
During operation, if the remote controller display shows [
P2
] or [
P8
] code, close valve A
immediately and refer to [Remote controller heating mode malfunction code].
Beware of the fan running when opening the front panel.
The fan may continue rotation after the system stops operating.
(8) When the required amount of refrigerant is charged, close valve A (See figure 30) (*8) and push
the RETURN button (BS3) once. And then go to procedure (9).
(9) Push the MODE button (BS1) once, and the charging is complete.
H1P H2P H3P H4P H5P H6P H7P
i
i
i
i
i
i
i
H1P H2P H3P H4P H5P H6P H7P
h
j
h
h
h
∗
∗
H1P H2P H3P H4P H5P H6P H7P
j
j
j
h
i
h
i
Go to
In case of
cooling mode
j
j
h
h
i
h
i
Go to
In case of
heating mode
H1P H2P H3P H4P H5P H6P H7P
i
j
j
i
i
i
i
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...