Field Setting
SiUS34-801A_b
254
VRVIII R-410A Heat Recovery 60Hz
Setting item 0 displays the contents of
various settings
EMG operation /
backup operation
setting
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Defrost select setting
Short
9 7 7 7 8 7 7
Medium
9 7 7 7 9 7 7
Long
9 7 7 7 7 7 7
Te setting
L
9 7 7 7 7 7 7
M
9 7 7 7 7 9 7
H
N
~
R
9 7 7 7 7 8 7
Tc setting
L
9 7 7 7 7 7 7
M
9 7 7 7 7 7 9
H
9 7 7 7 7 7 8
Data such as addresses and number of unitsare expressed as binary numbers; the two ways of
expressing are as follows:
The No. 1 cool/heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
In the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address
is 22.
The number of terminal blocks for No. 12 and 13 is expressed
as an 8-digit binary number, which is the combination of four
upper, and four lower digits for No. 12 and 13 respectively. (0 -
128)
In the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary
number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
See the preceding page for a list of data, for No. 0 - 25.
9 797997
16 4 1
32 8 2
977 7979
64 16
128 32
No.12
977 7997
4 1
No.13
8
2
Содержание VRV III
Страница 15: ...SiUS34 801A_b xiv ...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information ...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz ...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label ...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit ...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325 ...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A ...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640 ...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A ...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A ...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A ...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A ...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640 ...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A ...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A ...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A ...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix ...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix ...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A ...
Страница 563: ...SiUS34 801A_b iv Index ...