• HRV • Heat Reclaim Ventilation
37
• HRV • VAM-FA8VE
1
7
7
Product Specification
7-2
Optional accessories
7-2-4
KRP1B61: Interlock adapter of VRV
Electric Wiring
• Refer to the WIRING DIAGRAM attached to the indoor unit before attempting to wire.
[Make sure wires to units do not pass over the PC board when wiring.]
• Wire the adapter to the indoor unit as shown below,
1. Fetching the operation display signal
2. If optional accessories are installed (auxiliary electric heater, humidifier)
• Wire correctly in accordance with the attached installation manual.
• Refer to the wiring diagram applied to the indoor unit when running electric wiring.
• Attaching an hour meter
• Fan ON display
X16A
X2A
X1A
(HC0131)
Indoor unit PC board
Blue
Red
N
L
HM
AC
220 – 240 V
X2
X1
Output is generated at the contact while the
compressor is running.
(HC0132)
HM: Hour meter
(Part to be procured in the field)
Example :
RL
AC
220 – 240 V
X4
X3
Output is generated at the contact while the fan is
running.
(HC0133)
RL: Operation lamp
(Part to be procured in the field)
Example :
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...