• HRV • Heat Reclaim Ventilation
31
• HRV • VAM-FA8VE
1
7
7
Product Specification
7-2
Optional accessories
7-2-3
KRP2A51, KRP2A61: Wiring adapter for electrical appendices
1. Remote control input (operation control)
Wire as described below. Wiring differs depending on whether using a voltage or non-voltage input.
• For voltage input
• For non-voltage input
Wiring to external units (host computer monitor panel)
Set input changeover switch
(SS1) to “VOLT”.
(Factory set: VOLT)
Set input changeover switch
(SS1) to “NON VOLT”.
(Wiring specifications)
Wiring .... Sheathed wire
Gauge .... 0.18 ~ 1.25 mm
2
Length .... Max. 150 m
< IMPORTANT >
Keep transmission wiring at least 50 mm away from power
supply wiring to avoid malfunctions.
(HC0124)
NON
VOLT
VOLT
CHANGE OVER
BC
B2
B1
G
DC12-24V
Connect the control input to
the common contact (non-
polarity).
Use a 12-24 V external power supply.
Each contact requires approximately 10 mA,
therefore carefully select power supply
capacity.
Use a micro-current contact
of a minimum current load of
12 V, 1 mA or less.
Wiring adapter
KRP2A61 • 62 • 51 • 52
Input A
Input B
NON
VOLT
VOLT
CHANGE OVER
BC
B2
B1
G
DC12-24V
Wiring adapter
KRP2A61 • 62 • 51 • 52
Input A
Input B
Use a micro-current contact
of a minimum current load of
12 V, 1 mA or less.
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...