Control System
9-3
Applicable patterns
9-3-2
To connect the remote control to the HRV unit
(Part 1) single-group interlocked operation
(Part 2) Centralized control operation
Purposes and functions
When the HRV unit is interlocked to the single-group
control system, the remote control for HRV unit will be
connected to change the setting mode at the HRV unit side.
Cautions
1. It is not possible to set the “On / Off” and “timer” setting
by the remote control for HRV unit. Also it is not
possible to display the filter-sign and malfunction code
neither on the remote control for indoor unit nor on the
remote control for HRV unit.
2. Since this is two remote control system (for Indoor unit
and HR unit), the Master / Slave setting is required.
Example of control wiring
Switch setting of the HRV unit
• No change is required. (as per factory setting)
Optional accessories required
• Remote control BRC301B61
Purposes and functions
• Beside the operation by central remote control, the
remote control for HRV unit can change the ventilation
mode setting, the ventilation air flow setting and etc.
Cautions
1. In case of Zone control, the operation / stop and the
timer setting cannot be done by the remote control for
the HRV unit. (The operation lamp blinks twice to
indicate that the operation is not possible.)
2. The remote control for the HRV unit cannot set the
group no. for centralized control. In this case, the remote
control for the indoor unit has to be connected once for
this setting.
3. It is not possible to have Precool / preheat time setting
function.
Example of control wiring
Switch setting of the HRV unit
Group no. setting for central control is required.
It is necessary to set the group number for each unit
connected to the central transmission line (terminal no. (F1)
and (F2)).
Initial setting is required by the remote control for indoor
unit.
•
In case of collective / individual control
Collective zone interlock setting
................................................. “OFF” (as per factory set)
•
In case of zone control
Collective zone interlock setting
................................................. “ON” [17(27)·8·02]
Optional accessories required
• Remote control BRC301B61
Remote control for
Setting
Indoor unit
Slave
HRV unit
Master
X9A
X10A
X11A
J1 J2
F1 F2
P1 P2
P1 P2
JC
SS1
F1 F2
P1 P2
P1 P2
(HC0033)
HRV unit
Indoor unit
Remote control
for HRV unit
Remote control
for indoor unit
Connecting line can be
extended up to 500 m
maximum.
X9A
X10A
X11A
J1 J2
F1 F2
P1 P2
P1 P2
JC
SW
F1 F2
P1 P2
P1 P2
(HC0035)
To central control
HRV unit
Remote control
for HRV unit
Remote control
for indoor unit
Indoor unit
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...