2
9
• HRV
•
VKM-GA(M)V1
• HRV
•
Heat Reclaim Ventilation
243
9.9.9
Fresh-up Operation by External Input (HRV Unit)
PURPOSES AND FUNCTIONS
When the operation is interlocked with the local ventilating fan(such as the one for toilet or kitchen), the
HRV unit performs the over-supply operation to prevent inflow of the odor from outside.
The flow rate of supply air becomes higher than that of exhaust air.
Both the excessive supply mode (Supply Fresh-up) and the excessive exhaust mode (Exhaust Fresh-up)
are selectable.
In details, contact your dealer.
EXAMPLE OF CONTROL WIRING
Connecting line can be extended up to 50m maximum.
•
Local wiring
Note
The connecting wiring between HRV unit and the terminal for local connection can be extended up to 50m
maximum.
9.10
Field Setting and Test Run
9.10.1 Perform Field Settings with the Remote Controller
(1) Make sure the electric parts box lids are closed on the indoor and outdoor units.
(2) Depending on the type of installation, make the field settings from the remote controller after the
power is turned on, following the “Field Settings” manual which came with the remote
controller.
Lastly, make sure the customer
keeps the “Field Settings” manual,
along with the operating manual, in
a safe place.
Field setting
Using the remote controller of the VRV-system air conditioner to make HRV unit settings
〈
Initial setting
〉
•
“Mode No.” 17,18 and 19: Group control of HRV units.
•
“Mode No.” 27, 28 and 29: individual control
〈
Operating procedure
〉
The following describes the operating procedure and settings.
(1) Press the INSPECTION/TRIAL button for more than four seconds with the unit in the normal mode to
enter the local setting mode.
(2) Use the TEMPERATURE ADJUSTMENT button to select the desired “Mode No.”
(The code display will blink.)
(3) To make settings for individual units under group control (when mode No. 27, 28 or 29 is selected),
press the TIMER SETTING ON/OFF button to select the “unit No.” for which the settings are to be
made. (This process is not necessary when settings are made for the entire group.)
(4) Press the top section of the TIMER button to select the “FIRST CODE NO.”
(5) Press the lower section of the TIMER button to select “SECOND CODE NO.”
(6) Press the PROGRAM/CANCEL button once to enter the settings.
(The code display will stop blinking and light up.)
Operation of HRV unit
Terminal for local connection Capacity of connecting terminal
Fresh-up
Short-circuit
No-voltage normally open contact
for micro-current 12V, 1mA
Normal
Open circuit
J1 J2
F1 F2
P1 P2
P1 P2
JC
Remote controller
HRV unit
(Terminal for local connection)
SETTING
FIRST
CODE NO.
SECOND
CODE NO.
Mode No.
FIELD
SET MODE
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...