2
11
262
• HRV
•
VKM-GA(M)V1
• HRV
•
Heat Reclaim Ventilation
Required air flow based on tobacco smoking and odor
6-class odor level presentation (this classification is linked with an approximate, intuitive
estimation of gas concentration)
For example, to keep the odor level not greater than 2, the contamination concentration (tobacco
combustion amount (mg)/ventilation amount (m
3
)) should be reduced to 35.3 mg/m
3
or smaller. To keep
the odor level not greater than 1, the contamination concentration should be reduced to 17.7 mg/m
3
or
smaller. To calculate required air flow based on smoking concentration, use the following equation.
<Example>
Therefore, under the conditions given above, in the case of cleaning air using ventilation only, about 80 m
3
/
h/person of air flow is required. By using air cleaners and/or deodorizers in conjunction with the ventilation
system, its capacity can be reduced significantly.
Required air flow depending on the degree of smoking (estimated)
11.3
Calculation of Duct Pressure Loss
Some types of ventilating fans, including those (pressure types) installed in a cooking range hood, are
installed in a ducted system. The air flow depends on the pressure losses determined according to the
length of the ducted system and the number of bends, and other accessories contained in the system. Air
flow calculations should consider these pressure drops to estimate the air flow as accurately as possible.
Odor intensity
Description
0
Odorless
1
Manages to detect the presence of odor (threshold concentration)
2
Manages to detect what is producing the odor (threshold concentration)
3
Easily detects the odor
4
Strong odor
5
Very strong odor
Degree of smoking
Locations
Required air flow (m
3
/h/person),
minimum to recommended value
Smoking amount (number
of cigarettes/hour/person)
Very high
Dealer office, newspaper
editing room, meeting room
51~85
3~5.1
(1.5~2.5)
High
Bar, office, hotel
(guest room)
42~51
2.5~3
(1.3~1.5)
Medium (to high)
Restaurant, office
20~26
1.2~1.6
(0.6~0.8)
Low (sometimes)
Sales room in a bank,
office, shop
13~17
0.8~1.0
(0.4~0.5)
Tobacco combustion (mg/h · person)
Allowable contamination (mg/m
3
)
Q =
(m
3
/h)
1,000 × 0.7 × 4
35.3
Q =
= 79.3m
3
/h · person
Assumptions : Combustion per cigarette
1,000 mg
Combustion rate
70%
Number of cigarettes per person
4/h · person
Odor intensity level
2 (=35.5 mg/m
3
)
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...