• HRV • VKM-GAMV1
• HRV • Heat Reclaim Ventilation
170
2
7
7
Product Specification
7 - 1 VKM-GAMV1
7 - 1 - 3 Capacity tables
7 - 1 - 3 - 1 Cooling capacity tables
VKM-GA(M)
N
OTES
1
Cooling and heating capacities are based on the following conditons. Fan is based on High and Ultra-high? The figures in the parenthesis indicate
the heat reclaimed from the heat recovery ventilator. When calculating the capacity as indoor units, use the following figures:
VKM50GAMV1 : 3.5kW
VKM80GAMV1: 5,6kW
VKM100GAMV1 : 7.0kW
TC: Total capacity : kW; SHC : Sensible heat capacity : kW
Class
Capacity
Outdoor
°CDB
Coil Inlet air temp.°CDB
14.0WB
16.0WB
18.0WB
19.0WB
20.0WB
22.0WB
24.0WB
DX-Coil
Only
20.0DB
23.0DB
26.0DB
27.0DB
28.0DB
30.0DB
32.0DB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
50
2.8kW
index 25
10.0
1.9
1.5
2.3
1.8
2.6
2.0
2.8
2.0
—
—
—
—
—
—
12.0
1.9
1.5
2.3
1.8
2.6
2.0
2.8
2.0
—
—
—
—
—
—
14.0
1.9
1.5
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
—
—
—
—
16.0
1.9
1.5
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
—
—
—
—
18.0
1.9
1.5
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
—
—
—
—
20.0
1.9
1.5
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
—
—
—
—
21.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
—
—
—
—
23.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
2.1
—
—
25.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
2.0
—
—
27.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.2
2.0
—
—
29.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.2
2.0
—
—
31.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.1
2.0
—
—
33.0
—
—
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.1
2.0
3.1
1.8
35.0
—
—
—
—
2.6
2.0
2.8
2.0
3.0
2.0
3.0
1.9
3.1
1.8
37.0
—
—
—
—
2.6
2.0
2.8
2.0
2.9
2.0
3.0
1.9
3.0
1.8
39.0
—
—
—
—
2.6
2.0
2.8
2.0
2.9
2.0
2.9
1.9
3.0
1.8
80
4.5kW
index 40
10.0
3.0
2.1
3.6
2.4
4.2
2.7
4.5
2.7
—
—
—
—
—
—
12.0
3.0
2.1
3.6
2.4
4.2
2.7
4.5
2.7
—
—
—
—
—
—
14.0
3.0
2.1
3.6
2.4
4.2
2.7
4.5
2.7
4.8
3.3
—
—
—
—
16.0
3.0
2.1
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
—
—
—
—
18.0
3.0
2.1
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
—
—
—
—
20.0
3.0
2.1
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
—
—
—
—
21.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
—
—
—
—
23.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
5.3
2.9
—
—
25.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
5.2
2.9
—
—
27.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
5.1
2.8
—
—
29.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
5.1
2.8
—
—
31.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
5.0
2.8
—
—
33.0
—
—
3.6
2.4
4.2
2.7
4.5
2.7
4.8
2.8
4.9
2.7
5.0
2.6
35.0
—
—
—
—
4.2
2.7
4.5
2.7
4.7
2.8
4.8
2.7
4.9
2.6
37.0
—
—
—
—
4.2
2.7
4.5
2.7
4.6
2.8
4.8
2.7
4.9
2.6
39.0
—
—
—
—
4.2
2.7
4.5
2.7
4.6
2.7
4.7
2.6
4.8
2.5
100
5.6kW
index 50
10.0
3.8
2.5
4.5
2.9
5.2
3.3
—
—
—
—
—
—
—
—
12.0
3.8
2.5
4.5
2.9
5.2
3.3
5.6
3.3
—
—
—
—
—
—
14.0
3.8
2.5
4.5
2.9
5.2
3.3
5.6
3.3
—
—
—
—
—
—
16.0
3.8
2.5
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
—
—
—
—
18.0
3.8
2.5
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
—
—
—
—
20.0
3.8
2.5
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
—
—
—
—
21.0
—
—
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
—
—
—
—
23.0
—
—
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
—
—
—
—
25.0
—
—
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
6.5
3.5
—
—
27.0
—
—
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
6.4
3.5
—
—
29.0
—
—
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
6.3
3.4
—
—
31.0
—
—
4.5
2.9
5.2
3.3
5.6
3.3
6.0
3.4
6.2
3.4
—
—
33.0
—
—
—
—
5.2
3.3
5.6
3.3
6.0
3.4
6.1
3.3
6.3
3.2
35.0
—
—
—
—
5.2
3.3
5.6
3.3
5.9
3.3
6.0
3.3
6.2
3.2
37.0
—
—
—
—
5.2
3.3
5.6
3.3
5.8
3.3
5.9
3.2
6.1
3.1
39.0
—
—
—
—
5.2
3.3
5.6
3.3
5.7
3.3
5.8
3.2
6.0
3.1
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...