• HRV • VAM-FA8VE
• HRV • Heat Reclaim Ventilation
116
1
9
9
Control System
9-2
Basic patterns
Control
system
Purposes and applications
Description of system
Optional accessories
required
Interloc
ked operation
sy
st
em
wi
th
VR
V
sy
st
em
s an
d
Sk
yA
ir
se
rie
s
Interloc
ked operation wi
th 2
or
more
group
s
• When the HRV unit is interlocked to 2
or more groups of indoor units, The
HRV unit operates if one of indoor unit
in the groups is in operation. The HRV
unit can also be operated
independently by remote controller for
indoor unit, even if the indoor unit is
not in operation.
KRP2A61
♦
Adapter PCB for
remote control
(One adapter PCB
should be installed in
either the HRV unit or
the indoor unit.)
Cen
trali
zed contr
o
l s
ys
tem
Coolec
tive /
Individual co
ntrol
[Unified On / Off Controller]
• A maximum of 16 groups can be
controlled of “On / Off” by one controller,
and up to four controllers can be installed
in one system.
[Schedule Timer]
• One schedule timer can control the
weekly schedule of up to 128 units.
[Adapter PCB for remote
control]
• One adapter PCB can control up to
64 groups collectively.
DCS301B61
♦
Unified On / Off
Controller
(up to 4 controllers)
DST301B61
♦
Schedule timer
KRP2A61
♦
Adapter PCB for
remote control (not
possible to use together
with other central
controller)
* One of the above
controller should be
installed in indoor unit.
(However, only KRP2A61
can also be installed in HRV
unit.)
Zone co
ntrol s
ys
tem
• The Central remote controller can
control the zone operation of the
several groups of the units collectively.
• Central remote controller can control
the independent operation of HRV unit
in each zone.
DCS302B61
♦
Central remote
controller
Remote controller for indoor unit
Remote controller for indoor unit
Adapter PCB for remote conrol
Remote controller for indoor unit
Indoor unit
Indoor unit
Central transmission line
HRV unit
Remote controller for HRV unit
Remote controller for indoor unit
Indoor unit
HRV unit
Unified On / Off
controller or
Schedule timer
or Adapter PCB
for remote
Remote
controller for
indoor unit
Indoor unit
HRV unit
Remote controller for HRV unit
Remote controller for indoor unit
Indoor unit
HRV unit
Central
remote
controlle
r
Z
o
n
e
1
Indoor unit
HRV unit
Z
o
n
e
2
Remote controller for indoor unit
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...