• HRV
•
VKM-GA(M)V1
• HRV
•
Heat Reclaim Ventilation
9.9.5
Wiring Example
• This unit can be used as part of the combined operation system used together with indoor units
(VRV
III
system air conditioners), or as an independent system for processing outside air.
• When connecting with a cooling free building multi type and bringing the RA (exhaust gas intake) of
this unit directly in from the ceiling, connect to a BS unit identical to the building multi indoor unit
(master unit), and use group-linked operation. (See the Engineering Data for details.)
〈
Combined operation system with VRV
III
system (connected with HRV units and standard indoor units in a
single refrigerant circuit)
〉
〈
Independent system (connected only with a HRV unit in a single refrigerant circuit)
〉
F1 F2 F1 F2
R S
P1 P2 F1 F2 T1 T2
R S
P1 P2 F1 F2 T1 T2
L N
P1 P2 F1 F2 T1 T2
Transmission wiring
Outdoor unit
Fuse
Switch
Remote controller
Remote controller wiring
IN/D
OUT/D
Electric parts box
Standard indoor
unit A
Earth
Earth
Earth
Remote controller
Standard indoor
unit B
HRV A
(outside air
processing type)
Power supply
220-240V
~
50 Hz
Fuse
Switch
Power supply
220-240V
~
50 Hz
Fuse
Switch
Power supply
220-240V
~
50 Hz
F1 F2 F1 F2
R S
P1 P2 F1 F2 T1 T2
Transmission wiring
Outdoor unit
IN/D
OUT/D
Electric parts box
Standard indoor
unit A
Standard indoor
unit B
Earth
Earth
Earth
Remote controller
Remote controller
Remote controller
HRV A
(Outside air
processing or
standard type)
NOTE)
R S
P1 P2 F1 F2 T1 T2
L N P1 P2 F1 F2 T1 T2
NOTE) Standard type ........ VAM series
Fuse
Switch
Power supply
220-240V
~
50 Hz
Fuse
Switch
Power supply
220-240V
~
50 Hz
Fuse
Switch
Power supply
220-240V
~
50 Hz
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...