2
9
238
• HRV
•
VKM-GA(M)V1
• HRV
•
Heat Reclaim Ventilation
9.9.2
Connecting Power Supply Wiring and Ground Wiring
•
Pass the power supply wiring and the ground wiring through the wiring through-hole into the electrical
parts box and secure with the included clamping material after connecting the wires to terminal blocks.
(Refer to Fig. 17-1, 17-2)
〈
Precautions when laying power supply wiring
〉
[PRECAUTIONS]
[1] A circuit breaker capable of shutting down power supply to the entire system must be installed.
[2] A single switch can be used to supply power to units on the same system.
However branch switches, branch overload circuit interrupter must be selected carefully.
[3] Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
[4] Use round crimp-style terminals for connecting wires to the power supply terminal block.
If unavailable, observe the following points when wiring.
•
Do not connect wires of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.)
•
Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without
applying excessive force to the terminal. (Tightening torque: 131N·cm ±10%)
Short-circuit wire
Remove when installing
the humidistat
(locally procured).
Wiring for the humidistat
Clamp
Resin Clamp parts
Resin Clamp parts
Power supply wiring
Ground wiring
(accessory)
1 2 L N
L N
Grounging terminal
Terminal block (X1M) details
〈
VKM-GAMV1 series
〉
(M4 screws, spring
washers, cup washers)
Fig. 17-1
Clamp
Power supply wiring
Ground wiring
(accessory)
Grounging terminal
Terminal block (X1M) details
〈
VKM-GAV1 series
〉
(M4 screws, spring
washers, cup washers)
Fig. 17-2
Power supply wiring
Sheathed cable
(H05VV-03G)
Transmission wiring
Sheathed cable
Switch
Fuse
Power supply
Remote controller
VRV
Indoor unit
VRV
Indoor unit
VRV Outdoor unit
HRV (VKM)
HRV (VKM)
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...