Control System
9-3
Applicable patterns
9-3-4
Examples of mistakes in wiring and system designing
It is necessary to install the remote control for the transmission
line.
The centralized transmission line should be connected to
the indoor unit.
<Part 1>
• When you connect the transmission line for the remote
control, the remote control should be installed on the
transmission line.
Example of control wiring
Reason
Because the signal through the transmission line is
originated from the remote control, there is no transmission
signal to operate the units, if the remote control is not
installed.
<Part 2>
• If the HRV unit is interlocked to the centralized control,
the central transmission line should be connected to the
terminal no. F1 and F2 of indoor unit.
Example of control wiring
Reason
The information from the indoor unit cannot be
transmitted to the central control through the HRV unit.
And also the information from the central control cannot
be transmitted to the indoor unit through the HRV unit.
X9A
X14A
X15A
X17A
X10A
X11A
J1 J2
F1 F2
P1 P2
JC
SS1
F1 F2
P1 P2
(HC0041)
No remote control
HRV unit
Indoor unit
X9A
X10A
X11A
J1 J2
F1 F2
P1 P2
JC
SS1
F1 F2
P1 P2
P1 P2
(HC0042)
To central control
Centralized transmission line
HRV unit
Indoor unit
Remote control
for indoor unit
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...