The unit does not operate at all.
a. Check if there is a power failure.
Measure: After power has been restored, start operation again.
b. Check if the fuse has blown.
Measure: Turn the power off.
c. Check if breaker has worked.
Measure:Turn the power on with the breaker switch in the off position.
Do not turn the power on with the breaker switch in the trip
position. (Contact your dealer.)
•
If a safety device such as a fuse, a breaker, or an earth leakage
breaker frequency actuates, or ON/OFF switch does not properly work.
Measure: Do not turn the power on.
•
The remote control buttons do not work well.
Measure: Turn off the main power switch.
•
If the display “
” (INSPECTION), “UNIT No.”
and the OPERATION lamp flash and the
“MALFUNCTION CODE” appears.
Measure: Notify and inform the model name and
what the malfunction code indicates to
your Daikin dealer.
•
There are other malfunctions.
Measure: Stop the unit.
List of malfunction codes of Remote controller of the HRV-system
In case of the malfunction with the code in white letters on the black background in the unit still operates.
However, be sure to have it inspected and repaired and as soon as possible.
If other than the above error codes are displayed, there is a possibility that the problem in question
has occurred with a combined air conditioner or outdoor unit. See the operation manuals included
with the air conditioners or outdoor units for details.
Operation
lamp
Inspection
indicator
Unit No.
Malfunction
code
Description
On
Off
Blinking
64
Indoor air thermistor malfunction
On
Off
Blinking
65
Outdoor air thermistor malfunction
On
Off
Blinking
6A
Dumper-related malfunction
Blinking
Blinking
Blinking
6A
Dumper-related malfu thermistor malfunction
Blinking
Blinking
Blinking
A1
Printed circuit board fault
On
Off
Blinking
A1
Printed circuit board fault
Blinking
Blinking
Blinking
A9
Electric expansion valve drive error
Blinking
Blinking
Blinking
C4
Liquid piping thermistor error
(faulty connection, disconnection short circuit, fault)
Blinking
Blinking
Blinking
C5
Gas piping thermistor error
(faulty connection, cut wire, short circuit, fault)
Blinking
Blinking
Blinking
C9
Intake air into coil thermistor error
(faulty connection, disconnection, short circuit, fault)
Blinking
Blinking
Blinking
U3
Test run not performed
Blinking
Blinking
Blinking
U5
Transmission error between the unit and remote controller
Off
Blinking
Off
U5
Setting error of remote controller
Off
Blinking
Off
U8
Transmission error between main remote controller and
sub remote controller
Off
Blinking
Blinking
UA
Incorrect combination with indoor unit and remote controller.
On
Blinking
On
UC
Central control address over lapping
Blinking
Blinking
Blinking
UE
Transmission error between the unit and centralized
controller
Switch
ON
OFF
Trip position
Breaker
INSPECTION display
MALFUNCTION CODE
INDOOR UNIT No. in
which a malfunction occurs
OPERATION lamp
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...