Product Specification
7 - 2 VKM-GAV1
7 - 2 - 9 Installation
7 - 2 - 9 - 1 Installation method
VKM100GAV1
3D051324
NOTES
1
Leave space for servicing the unit and include inspection hatch.
(Always open a hole on the side of the control box so that the air
filters, heat exchange elements, and fans can easily be inspected
and serviced.)
2
Install the two outdoor ducts with down slope (slope of 1/30 or more)
to prevent entry of rain water, also, provide insulation for three ducts
(outdoor ducts and indoor supply air duct) to prevent dew
condensation) (material: glass wool of 25mm thick).
3
Do not turn the unit upside down.
4
Make sure install drain piping, and insulate drain piping to prevent
dew condensation.
5
Keep the drain pipe short and sloping downwards at a gradient of at
least 1/100 to prevent air from forming.
6
Do not use a bent cap or a round hood as the outdoor hood if they
might get rained on directly (we recommend using a deep hood)
(optional accessory).
7
In areas where freezing may occur, always take steps to prevent the
pipes from freezing.
8
Do not place something which shouldn’t be get wet at the below of
this unit. The dew would fall at following case, where humidity is 80%
more, or the exit of drain socket is choked up, or the air filter is very
dirty.
1262
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Inspection
hatch
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier
360 (In case of
450 inspection hatch)
140 (In case of
600 inspection hatch)
Inspection
hatch
Round shape hood
(Locally procured)
1688
Heat insulator
(Locally procured)
Air suction grille
(Locally procured)
Flexible duct
(Locally procured)
Heat insulator
(Locally procured)
Air discharge grille
(Locally procured)
Air discharge grille
(Locally procured)
150~250
More
than 600
Control box
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
ø200
Nominal diameter
(Locally procured)
Branch duct
(Locally procured)
A gradient of
more than 1/30
Refrigerant piping (gas pipe)
(ø12.7 flare connection)
Refrigerant piping (liquid pipe)
(ø6.4 flare connection)
Suspension bolt
(Locally procured)
450 • 600
inspection hatch
(Locally procured)
RA
(Return air from room)
SA
(Supply air to room)
Sloping downards at a
gradient of the 1/100
Silencer
(Locally procured)
Содержание VAM-FA8VE
Страница 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Страница 2: ......
Страница 152: ......
Страница 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Страница 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...
Страница 279: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 277 R 410A Saturation pressure gauge pressure chart ...
Страница 281: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 279 Pressure enthalpy curves of HFC32 125 50 50 wt Z0169 R 410A ...