background image

Operating instructions

A3G630-AD03-A1

Translation of the original operating instructions

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com

CONTENTS

1. SAFETY REGULATIONS AND NOTES

1

1. SAFETY REGULATIONS AND NOTES

Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.

1.1 Levels of hazard warnings

1

1.1 Levels of hazard warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.

WARNING

Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualification

1

1.2 Staff qualification

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by qualified, trained and authorised
technical staff.
Only authorised specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:

;

Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.

1.4 Electrical voltage

1

1.4 Electrical voltage

;

Check the electrical equipment of the device at regular intervals, refer
to chapter 6.2 Safety test.

;

Replace loose connections and defective cables immediately.

DANGER
Electrical load on the device

Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically

charged device.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

2

1.5 Safety and protective functions

2

1.6 Electromagnetic radiation

2

1.7 Mechanical movement

2

1.8 Emission

2

1.9 Hot surface

2

1.10 Transport

2

1.11 Storage

3

2. PROPER USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Data in accordance with ecodesign regulation EU 327/2011

5

3.4 Technical features

6

3.5 Mounting data

6

3.6 Transport and storage conditions

6

3.7 Electromagnetic compatibility

6

4. CONNECTION AND START-UP

6

4.1 Connecting the mechanical system

6

4.2 Connecting the electrical system

7

4.3 Connection of the cables

8

4.4 Factory settings

9

4.5 Connection screen

10

4.6 Checking the connections

10

4.7 Switch on device

10

4.8 Switching off the device

10

5. INTEGRATED PROTECTIVE FUNCTIONS

10

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

11

6.1 Cleaning

11

6.2 Safety test

11

6.3 Disposal

Item no. 50323-5-9970 · ENG · Revision 89187 · Release 2016-04-14 · Page 1 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G630-AD03-A1

Страница 1: ...device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once...

Страница 2: ...device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impell...

Страница 3: ...device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibration...

Страница 4: ...n of air flow V 2 Depth of screw max 10 mm 3 Connection line PVC AWG18 5 x crimped core end sleeve 4 Connection line PVC AWG22 3x crimped core end sleeves Item no 50323 5 9970 ENG Revision 89187 Relea...

Страница 5: ...finition with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 5 8 kg Size 630 mm Surface of rot...

Страница 6: ...be damaged Set down the fan carefully on a soft surface Make sure the blades are not subjected to load After installation make sure the impeller moves easily and that the blades of the impeller are n...

Страница 7: ...witched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If th...

Страница 8: ...th which the device is pre set by ebm papst Operation mode PWM controlling Group adress 01 Fan device adress 01 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value control Analog Control funct...

Страница 9: ...connection 2 A max 250 VAC min 10 mA 1 6 NC white 2 Floating status message contact normally closed connection 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 VDC re...

Страница 10: ...ct the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to s...

Страница 11: ...sary Visual inspection At least every 6 months Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace device Abnormal bearing noise acoustic At least every 6...

Страница 12: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for internal wiring Electrolytic...

Отзывы: